Cummins Generator SPN 94 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover what the Cummins Generator SPN 94 FMI 4 error code means, its common causes, and step-by-step solutions. Quickly diagnose and fix your generator issues with this easy guide.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the SPN 94 FMI 4 error code on Cummins a Generator mean?

 

Understanding the SPN 94 FMI 4 Error Code on a Generator

 

When a generator shows the SPN 94 FMI 4 error code, it is alerting you to a specific electrical issue: the engine control module is detecting a low voltage level from the engine’s battery or power supply. Simply put, “SPN 94” points to a problem with the battery voltage sensor, and “FMI 4” means the voltage is lower than it should be. This isn’t just a minor glitch—if this problem continues, your generator in St. Louis or Nashville might not start, shut down unexpectedly, or fail to provide electricity when you need it most.

 

Breaking Down the Error Code: What Each Part Means

 

  • SPN (Suspect Parameter Number) 94: This is an international code used by engine and generator manufacturers. SPN 94 always relates to the battery supply voltage—the health and performance of the battery supplying power to the generator’s control system.
  • FMI (Failure Mode Indicator) 4: This means "Voltage Below Normal" (but not zero). It tells you the control module is receiving less voltage than required for reliable operation.

Combined, SPN 94 FMI 4 is warning you that the control system—the “brain” of your generator—isn’t getting enough electrical energy from the battery to run properly.

 

Why This Problem Matters for Your Home or Business

 

Generators depend on reliable battery voltage for several crucial functions:

  • Starting the engine: Low voltage might mean your generator in St. Louis or Nashville won’t start during a power outage.
  • Consistent operation: The electronic controls and safety systems need stable voltage to monitor and manage the generator safely.
  • Protecting equipment: Running on low voltage can cause other sensitive electronics to malfunction or become damaged over time.

Ignoring this code could leave you without backup power when you need it most, which is especially critical during storm seasons or busy business operations in places like St. Louis and Nashville.

 

What Causes the SPN 94 FMI 4 Error Code?

 

The generator is signaling that something is wrong in the battery supply circuit. Common reasons include:

  • Weak or dead battery: Over time, batteries lose their ability to hold charge. If your generator battery is old (usually over 2-3 years), it might not supply enough voltage.
  • Loose or corroded cables/connectors: Battery cables can develop rust or loosen up, breaking a continuous flow of power to the generator.
  • Faulty charging system: The alternator or battery charger inside the generator may not be recharging the battery properly, so voltage drops.
  • Parasitic drains: Sometimes, accessories or internal electronics can slowly drain power from the battery even when the generator’s not running.
  • Extreme temperatures: Intense cold or heat in St. Louis or Nashville can affect battery performance, making low voltage more likely.
  • Wiring or sensor failure: The sensor that measures voltage itself, or the wires leading to the engine control module, can go bad or break, causing false alarms or real failures.

 

What Should You Do If You See This Code?

 

If SPN 94 FMI 4 appears, follow these steps:

  • Check the battery: Look for corrosion, loose cables, or obvious physical damage. Use a simple voltmeter to check the battery voltage. A healthy, fully charged battery usually reads about 12.6 volts or higher.
  • Test battery under load: Sometimes a battery looks okay until you put a load on it (try starting the generator). If voltage drops dramatically, the battery may need to be replaced.
  • Inspect connections: Make sure all terminals fit tightly and there’s no rust or build-up. Clean with a wire brush and re-tighten as needed.
  • Check the charger: If your generator has an automatic battery charger, make sure it’s plugged in and working. You might need a technician who understands local conditions in St. Louis or Nashville to test and replace charging components if necessary.
  • Consult a professional: If you are unsure or the error doesn’t resolve, contact a qualified generator service provider. Specialists can diagnose hidden wiring or sensor faults and prevent bigger issues down the road.

 

How to Prevent This Error Code in the Future

 

Preventing battery voltage issues is mainly about simple, routine maintenance:

  • Test and replace batteries every 2-3 years, especially in climate-challenged areas like St. Louis and Nashville.
  • Keep battery terminals and connections tight and clean.
  • Regularly check the generator’s charging system during seasonal maintenance checks.
  • Look out for warning lights or odd behaviors (slow cranking, dim displays) during generator tests.
  • Ask your local service provider to inspect and test critical electrical components annually.

By understanding and addressing the SPN 94 FMI 4 error code, you help ensure your generator remains reliable for your family or business in both St. Louis and Nashville, especially when you need it most.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the SPN 94 FMI 4 Error on a Cummins Generator?

 

What Does SPN 94 FMI 4 Mean on a Cummins Generator?

 

If your Cummins generator is displaying the SPN 94 FMI 4 error code, it means there's a problem with low battery voltage detected by the engine control module. SPN stands for Suspect Parameter Number (which is the location of the issue), 94 is the code for the battery voltage, and FMI 4 refers to a voltage below the normal operating range. This is a warning—it generally means your generator’s battery isn't getting or holding a proper charge, or there is an electrical connection issue.

 

Immediate Actions to Take for SPN 94 FMI 4 Error

 

When you see this error, start by turning off your generator if it’s safe to do so. Safety always comes first. You want to prevent additional electrical stress or damage to the generator's sensitive components.

 

Steps to Fix the SPN 94 FMI 4 Error

 

  • Check the Battery Voltage Directly
    Use a basic multimeter (a tool that measures electrical voltage) to check the voltage across the battery terminals. For most Cummins generators, a healthy battery should show about 12.6 to 12.8 volts when the engine is off. If it’s much lower (especially below 12 volts), the battery is likely discharged or faulty.
  • Inspect Battery Terminals and Connections
    Look at the battery terminals—these are where the generator’s wires connect to the battery. Check that the terminals are tightly connected and clean, without corrosion (white or greenish build-up). If you see corrosion, disconnect the battery (always remove the negative/black cable first), then clean the terminals and cable ends using a wire brush or battery terminal cleaner.
  • Examine Battery Cables and Wires
    Inspect all cables running from battery to the generator. Make sure there are no loose, frayed, or damaged wires. Pay special attention to the cable crimp connections and that all bolts are snug. A single loose connection can cause this fault.
  • Test Battery Health
    If the battery voltage is low, try to charge it with a battery charger. After charging, disconnect the charger and let the battery sit for about half an hour, then measure again. If it drops quickly back below 12 volts, the battery may need to be replaced. Replacement is usually straightforward, but be sure to get the correct Cold Cranking Amps (CCA) and voltage for your Cummins generator.
  • Inspect the Alternator and Charging System
    When the generator is running, the alternator is responsible for recharging the battery. Use your multimeter to measure voltage at the battery with the generator running—expect 13.5-14.5 volts. If you’re not seeing a voltage increase, there may be a charging system problem, such as a bad alternator, faulty voltage regulator, or wiring issue.
  • Check for Parasitic Drains
    Sometimes, things like faulty relays or control boards may be draining the battery even when the generator is off. With the generator off, disconnect the negative battery cable, and use a multimeter in “amps” mode between the cable and the battery post. If you see a steady drain, you’ll need to trace and isolate the culprit, possibly with the help of a technician.
  • Review Recent Service or Changes
    If you’ve recently had work done on your generator, double-check that all battery and alternator connections were properly reattached. Something may have been left loose.

 

When to Call a Professional Technician

 

If these checks don't resolve the warning, or you aren’t comfortable with electrical work, it's time to contact a professional who understands Cummins generators. In both St Louis and Nashville, it's important to choose a service team that understands your specific generator brand and can safely handle electrical diagnostics. An expert technician will have advanced equipment to check the generator control modules for stored fault codes and use factory-approved tests.

They can also spot less common issues, like hidden wiring faults, charging circuit failures, or software glitches in the control system that could also result in SPN 94 FMI 4. Reliable companies in St Louis and Nashville should be familiar with both commercial and residential generator systems.

 

Tips to Prevent SPN 94 FMI 4 in the Future

 

  • Keep battery terminals clean and free from corrosion.
  • Test your generator battery at least once a year to ensure it holds a charge.
  • Ensure generator exercise cycles (automatic weekly run) are enabled; they help keep the battery charged.
  • Check the generator's charging system as part of regular service.
  • Replace worn-out batteries promptly—don’t wait for them to completely fail.

By following this process, most SPN 94 FMI 4 errors can be tracked down to either a simple battery issue or an obvious wiring connection. If your generator powers critical loads at your home or business in St Louis or Nashville, fast resolution is important. Never ignore this error, as low battery voltage can lead to more serious generator problems down the line.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the SPN 94 FMI 4 error code on a Cummins Generator?

 

Understanding the SPN 94 FMI 4 Error Code on Cummins Generators

 

If you are seeing the SPN 94 FMI 4 code on your Cummins generator, it means there is an issue with the fuel delivery system—specifically, this code signals that there is a problem with the fuel pressure being lower than what the engine expects while it's running. This warning is critical because the generator relies on precise fuel pressure to run efficiently and safely. For homeowners and businesses in St Louis and Nashville, understanding this code will help in communicating clearly with your professional technician.

 

What Do SPN 94 and FMI 4 Mean?

 

  • SPN 94 stands for "Fuel Delivery Pressure." SPN stands for Suspect Parameter Number—it's a code used by the engine control computer to pinpoint which part of the system is having trouble.
  • FMI 4 means "Voltage Below Normal or Shorted to Low Source." FMI stands for Failure Mode Identifier and reveals how the fault is showing up. In this case, the system is saying it detects the fuel pressure is below normal limits.

So together, these codes mean the generator’s engine computer thinks the fuel delivery pressure is too low during operation. Sometimes, the generator might shut down to prevent engine damage or stay running in a reduced power mode.

 

Why Does Low Fuel Pressure Happen in Cummins Generators?

 

A fuel system works by pulling fuel from the tank, pushing it through filters, then sending it under pressure to the engine. If something interferes with that process, the pressure drops. Some very common causes seen in St Louis or Nashville include:

  • Clogged Fuel Filter: The fuel filter is meant to trap dirt and debris before they enter the engine. If it becomes too dirty, fuel can’t pass through quickly enough, dropping the pressure.
  • Leaking or Cracked Fuel Lines: Any cracks or leaks in the metal or rubber lines running from the tank to the engine can let air in or fuel out, reducing pressure. Leaks also pose a fire risk.
  • Failing Fuel Pump: The fuel pump is responsible for creating the pressure necessary for the generator to operate. If it wears out or gets blocked, it can’t push enough fuel through.
  • Faulty Fuel Rail Pressure Sensor: The sensor monitors the fuel system pressure and provides data to the engine’s computer. If this sensor fails, it might mistakenly signal low pressure even if the fuel system is performing correctly, or it might not detect real pressure problems as they develop.
  • Air in the Fuel System: If recent maintenance has been performed, or if there is a loose connection somewhere, air bubbles can get into the system, leading to low fuel pressure readings.
  • Fuel Contamination: Water, algae, or other contaminants in the fuel can clog filters or damage the pump, all resulting in lower pressure.
  • Restricted Fuel Tank Vents: Fuel tanks need to be vented so air can replace fuel as it is used. If the vent is blocked, the tank can develop a vacuum that slows fuel flow.
  • Electrical Issues: Problems with wiring or connectors leading to the fuel pump or pressure sensor can also cause the computer to read a false low pressure, or might prevent proper operation of the pump.

 

How the Error Impacts Generator Operation in St Louis and Nashville

 

In both St Louis and Nashville climates, generators are often called upon during storms, heat waves, or unexpected power outages. Low fuel pressure, as indicated by the SPN 94 FMI 4 code, means the generator may not deliver full power or could shut down entirely—which could be disruptive, especially in areas prone to severe weather or long utility outages.

If this issue arises, it’s important not to ignore it. The error code is the generator’s built-in safety feature, helping to prevent engine damage from low fuel flow or from contaminants entering the delicate parts of the engine.

 

Summary of Possible Causes for SPN 94 FMI 4

 

  • Dirty or blocked fuel filter stopping fuel flow
  • Cracked, leaky, or disconnected fuel hoses
  • Malfunctioning or failing fuel pump
  • Faulty fuel pressure sensor sending wrong signals
  • Contaminated fuel (water, debris, microbial growth)
  • Blocked fuel tank vent leading to vacuum inside the tank
  • Electrical faults in the wiring or connectors involved in the fuel system
  • Recent maintenance introducing air or causing loose connections

If you’re seeing this code on your Cummins generator in St Louis or Nashville, the central message is that the generator isn’t getting the fuel pressure it needs to operate safely and efficiently, and professional investigation is essential to protect your equipment and ensure reliable power.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.