Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the SPN 175 FMI 3 error code on Cummins a Generator mean?

 

What the SPN 175 FMI 3 Error Code Means on a Generator

 

When you see the error code SPN 175 FMI 3 on your generator, it specifically points to an issue with the generator’s engine coolant temperature sensor circuit. In plain terms, this code is your generator’s way of saying there’s an electrical problem with the sensor that monitors how hot or cold your engine’s coolant is running. More precisely, FMI 3 means there is a voltage reading that is higher than normal in this sensor’s circuit. This can be caused by a wiring fault, a disconnected plug, a sensor failure, or sometimes even an issue with the main engine control module.

Residents and business owners in both St Louis and Nashville often rely on their backup generators for power during outages or emergencies. This particular error can put your generator out of commission, so it’s helpful to understand what’s going on and what steps to take next.

 

What the Engine Coolant Temperature Sensor Does

 

The engine coolant temperature sensor’s job is to keep track of the temperature of the coolant in your generator’s engine. Coolant is a special fluid that flows around the engine to keep it from getting too hot. If the coolant gets too hot, it can damage the engine. If it’s too cold, the engine may not run efficiently. The sensor sends its temperature readings to the generator’s computer so the system can make adjustments or trigger shutdowns if things get too hot.

When the generator’s system can’t read the sensor properly—either because of wiring damage, corrosion, a loose connector, or a failed sensor—it triggers codes like SPN 175 FMI 3. The “SPN” part stands for “Suspect Parameter Number” and refers to the specific system being monitored, and “FMI” stands for “Failure Mode Identifier,” which describes the kind of problem the system found. In this case, FMI 3 means an “above normal voltage,” which usually suggests an open circuit or broken connection.

 

Common Causes for SPN 175 FMI 3 Error Code

 

  • Wiring Problems: Sometimes, wires can get damaged by rodents, water, or vibration. Damaged wires might break the connection between the sensor and the generator’s computer.
  • Loose or Corroded Connections: Connectors can get loose due to movement or simply from years of use. Corrosion from moisture is especially common in climates like those in St Louis and Nashville.
  • Failed Sensor: The sensor itself can fail over time, especially if exposed to engine heat or coolant leaks.
  • Faulty Engine Control Module: Though rare, the generator’s main control module might develop a fault that shows up as a sensor issue.

 

What Should You Do If You See This Code?

 

  • Turn Off the Generator: If possible and safe, turn off your generator to prevent engine damage.
  • Check for Obvious Issues: Look for damaged wires, loose connectors, or leaks around the sensor. If you feel comfortable, visually inspect the wiring harness near the engine, but only when the generator is off and cool.
  • Do Not Ignore the Warning: Ignoring this issue can lead to the generator shutting down when you need it most, or even costly engine damage if overheating occurs.
  • Contact a Professional: Generators are complex, and electrical diagnostics often require special tools. If you’re in St Louis or Nashville, having an experienced technician check your generator ensures the right diagnosis and safe repair.

 

How a Technician Will Fix It

 

A certified technician will typically start by scanning the generator’s onboard computer for any stored codes and then visually inspecting the sensor and wiring. Using tools like a multimeter, they’ll test for proper voltage and continuity in the sensor circuit. If a damaged wire or connector is found, it will be repaired or replaced. If the sensor itself is faulty, it will be replaced. In very rare cases, the main computer may need service. The technician will clear the error code and test the generator to ensure correct operation before finishing.

 

Preventing SPN 175 FMI 3 and Similar Generator Errors

 

Generators require regular maintenance just like cars do. Regular checks help identify worn wiring, leaking coolant, or dirty sensors before they become major problems. Scheduling annual generator maintenance gives peace of mind, especially in areas like St Louis and Nashville where severe weather or outages are not uncommon. Regular servicing includes checking all sensor connectors, testing wiring, inspecting for rodents or damage, and ensuring engine coolant is at the right level and quality.

 

In Summary

 

SPN 175 FMI 3 means your generator is alerting you to an electrical problem with the engine coolant temperature sensor, most often a broken or disconnected wire, corroded connection, or a failed sensor. Don’t ignore this warning—it protects your generator’s engine from overheating and major damage. Safely shut down the unit if you see this code, look for any obvious issues if you’re comfortable doing so, and contact a qualified service provider familiar with generators in St Louis and Nashville to perform a thorough inspection and repair. Regular maintenance is the best way to prevent this and other error codes from disrupting your power supply.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the SPN 175 FMI 3 Error on a Cummins Generator?

 

Understanding and Fixing SPN 175 FMI 3 Error on a Cummins Generator

 

The SPN 175 FMI 3 code on a Cummins generator is an alert that there’s an issue with the battery voltage sensor circuit. Specifically, this error means the Engine Control Module (ECM) is detecting that the battery voltage is above the normal range. In other words, your generator believes it’s seeing a battery voltage that’s too high, which can cause serious damage if not addressed. If you are in St Louis or Nashville, it’s important to handle this promptly, as a generator with battery issues may fail to start or run safely.

 

What Causes the SPN 175 FMI 3 Error?

 

This code is most often triggered by:

  • Faulty battery or battery charger pushing voltage too high.
  • Malfunctioning alternator or voltage regulator.
  • Bad connections, especially corroded or loose wiring on the battery terminals.
  • Damaged or malfunctioning ECM sensing circuits.
  • Incorrect generator or battery installation.
You might notice other symptoms as well, like flickering lights on the control panel, alarms, or even failure to start.

 

How to Fix the SPN 175 FMI 3 Error

 

Here’s a practical, step-by-step approach that a homeowner or maintenance staff in St Louis or Nashville can use to address the issue:

  • Turn Off Power for Safety Before touching any part of the generator, make sure the unit is turned off completely and isolated from power. This prevents injury and accidental shorting.
  • Check Battery Voltage with a Multimeter A healthy 12V battery should show between 12.4V and 12.7V when the generator is off. If your reading is above 14.5V while engine runs or much higher while off, you have a problem.
  • Inspect Battery and Connections Look closely at the battery terminals for corrosion (white or greenish powder), loose wires, or frayed cables. Clean all terminals using a wire brush, and ensure all connections are tight. If you spot any damaged wires or cracked insulation, repair or replace them.
  • Check Battery Charger (If Installed) Many standby generators use battery chargers to keep the battery topped up. Check if the charger is set to the correct battery type and charge rate. Use a multimeter to confirm the charger output is not overcharging. If the charger is faulty or set incorrectly, repair or replace it.
  • Inspect Alternator and Voltage Regulator If the generator is running and showing high voltage, the alternator or its regulator may be the issue. A mechanic or generator professional in St Louis or Nashville can test the regulator’s output and the alternator’s field coil for failures.
  • Check ECM Sensing Wires Trace the wires from the battery to the ECM. Look for pinched, damaged, or disconnected wires. Sometimes rodents can chew on wires, or they might simply wear over time. Repair any wiring problems found.
  • Test or Replace the Battery Old batteries can develop internal faults and overvolt. If the battery is more than three years old, or if it fails a load test (any auto parts store or generator professional can test it), replace with a quality unit suited for your generator’s specifications.
  • Scan and Clear Codes Once repairs are complete, use the generator’s onboard display or a diagnostic tool to clear the code. Run the generator and keep an eye on the voltage readings and the control panel for any repeat of the fault.

If you don’t have the tools or experience to handle these tasks, calling a local generator expert in St Louis or Nashville is a smart choice. Improper handling of generator wiring can cause personal harm or additional damage.

 

Prevention Tips After Repair

 

  • Do regular inspections of the battery and connections – at least once a year or after heavy storms.
  • Make sure your battery charger is matched to your battery type.
  • Keep your generator serviced by professionals, especially before harsh weather seasons in St Louis or Nashville.
  • Test start your generator monthly if it's for standby use.

By tackling the SPN 175 FMI 3 code in these ways, you ensure your Cummins generator will be reliable whenever you need it most, whether you’re at home or running a business in St Louis or Nashville.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the SPN 175 FMI 3 error code on a Cummins Generator?

 

What Causes the SPN 175 FMI 3 Error Code on a Cummins Generator?

 

The SPN 175 FMI 3 error code on a Cummins generator usually signals a voltage-related issue with the engine’s coolant temperature sensor. In everyday language, this means the generator is detecting a problem with how it monitors the temperature of its engine coolant. It is not actually reporting that the engine is too hot or too cold, but instead that the generator’s computer is receiving an electrical signal from the sensor that doesn’t make sense—specifically, the voltage is higher than normal, indicating a possible electrical fault. This helps protect your equipment from damage and ensures reliability for residents and businesses in both St Louis and Nashville.

 

Breaking Down the Error Code

 

  • SPN (Suspect Parameter Number) 175: This is the code the generator uses to identify the coolant temperature sensor. The coolant temperature sensor keeps track of how hot or cold the engine’s coolant is.
  • FMI (Failure Mode Identifier) 3: This number tells us there is a voltage issue on the sensor’s signal wire. FMI 3 specifically means that the electric signal coming from the coolant temperature sensor is higher than it should be, possibly much higher.

 

Detailed Explanation of Causes

 

When SPN 175 FMI 3 appears, it is commonly caused by one of these factors:

  • Wiring Problems: The wires that connect the coolant temperature sensor to the generator’s computer might be damaged, broken, or not connected properly. In St Louis or Nashville, things like vibration, rodents, or aging equipment can cause these electrical wires to wear out or separate.
  • Sensor Malfunction: The coolant temperature sensor itself could be faulty. Over time, these sensors can fail due to age, constant exposure to hot and cold, or electrical surges. A broken sensor often sends the wrong voltage back to the generator’s control system.
  • Corroded or Loose Connections: Moisture—common during humid St Louis summers or rainy weather in Nashville—can lead to rust or corrosion on the sensor’s connectors. This corrosion can interrupt the electric flow and send strange signals, leading the system to show this error.
  • Computer (ECU) Issues: While not as common, sometimes the generator’s own computer (also called the Engine Control Unit or ECU) malfunctions. This would cause it to read even a good signal as incorrect. Usually, though, the problem is with the sensor or wiring, not the computer itself.
  • Electrical Short or Open Circuit: If the wire carrying information from the sensor is touching another wire (short) or is completely disconnected (open), this will result in odd voltage readings. Mechanics often find broken clips, old insulation, or improperly routed wires as culprits.

 

Why This Matters for You

 

In simple terms, the generator might not know how hot it’s getting, putting your power supply at risk. Since commercial and home generators in St Louis and Nashville rely on these sensors to protect engines from overheating, ignoring the issue can cause more serious problems down the line.

The SPN 175 FMI 3 code does not mean the generator will stop immediately, but it does mean the brains of the generator aren’t getting correct information about engine temperature. That’s why it’s important to catch and understand this code—it’s about protecting your generator’s most critical parts.

 

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.