Kohler Generator Code 13 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 13 means, common causes behind this error, and step-by-step solutions to fix it. Keep your generator running smoothly with our expert guidance.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the Code 13 error code on Kohler a Generator mean?

 

What Generator Code 13 Means and Why You Shouldn’t Ignore It

 

When a generator displays a Code 13 error, it is telling you that the engine is running at too high an RPM (Revolutions Per Minute), which is also called “Over Speed.” In simple words, the motor inside your generator is spinning faster than it should. Most standby generators, like the ones used in homes and businesses across St. Louis and Nashville, are set to operate at a precise speed. When this speed gets too high, it can cause various mechanical problems, so the generator’s computer system immediately shuts down the machine and displays this code to protect it from damage.

 

Understanding “Over Speed” and What Causes It

 

The generator’s engine operates similarly to your vehicle’s engine, with a precise control over how fast it spins. If it goes above that safe speed for even a few seconds, it can lead to serious wear, overheating, or even engine failure.

There are several common reasons why a Code 13, or Over Speed, error might occur, including:

  • Faulty governor control: The governor is a device that regulates and keeps the engine speed steady. If it fails, the engine can rev higher than normal.
  • Problem with the throttle linkage: If a throttle cable or connection is stuck, loose, or broken, the engine might get more fuel than it should, causing it to speed up.
  • Incorrect or failed speed sensor: Modern generators use sensors to track the engine RPM. If the sensor gives the wrong reading, or breaks altogether, it can cause an Over Speed error by mistake or by failing to control RPM.
  • Electrical issues: In rare cases, problems in the control circuit or wiring can interrupt the normal signals and lead to a speed mismatch, resulting in this error code.
  • Sudden loss of load: If the generator is powering heavy equipment in a St. Louis business or a busy Nashville hospital and the load drops instantly (like a large device is turned off), the engine may speed up briefly until the governor adjusts.

 

Why Over Speed is Dangerous

 

When a generator’s engine operates above its intended range, several risks are present:

  • Potential damage to the alternator (the component that produces electricity)
  • Increased wear and tear on moving engine parts
  • Possible catastrophic failure, including thrown connecting rods or cracked components, if left unchecked
  • Safety hazards due to overheating or mechanical breakage, especially in community buildings in St. Louis or commercial sites throughout Nashville

That’s why the onboard computer acts fast—shutting down the engine and issuing the Code 13 error before anything worse can happen.

 

What to Do If You See a Code 13 Error on Your Generator

 

If you see Code 13 on your generator control panel:

  • Don’t try to restart the generator repeatedly. Each time you do, it may trigger another over speed event and cause more damage.
  • Check for visible issues. If you are comfortable and it is safe, inspect for obvious problems like broken or loose wires, disconnected sensors, or a stuck throttle linkage in the generator’s engine compartment.
  • Don’t remove the covers or attempt repairs yourself. Generators operate at high voltage and spinning speed. Without the right training and tools, it’s safer not to attempt in-depth troubleshooting.
  • Call a qualified generator technician. This is a situation best left to professionals with specialized knowledge and equipment. If you’re in St. Louis or Nashville, it’s recommended to contact an experienced team familiar with your specific generator model and local power standards.

 

How Professionals Diagnose and Fix a Code 13 Error

 

When trained technicians arrive, they will:

  • Use diagnostic tools to read saved error data and live operating values from your generator’s control board.
  • Physically inspect the governor, throttle assembly, and speed sensor.
  • Test the sensor signals with a multimeter or diagnostic software to find if the readings are within factory specifications.
  • Check wiring integrity to rule out loose or corroded electrical connections—typical in places with high humidity or temperature swings, like St. Louis and Nashville.
  • Suggest component replacement, sensor recalibration, cable repairs, or full part swaps, as needed for safe operation.

If your generator is still under warranty, professional repair ensures coverage is not voided, and future reliability is protected.

 

Preventing Future Code 13 (Over Speed) Errors

 

You can lower the chances of seeing a Code 13 error by:

  • Scheduling routine generator maintenance at least once per year.
  • Having the speed sensor, throttle, and governor inspected regularly.
  • Testing the generator under load to confirm it holds a steady speed—an important consideration for properties with varying power needs in St. Louis and Nashville.
  • Keeping the generator clean and its airways clear—debris can sometimes interfere with moving parts.

Early detection of small issues during maintenance—like minor sensor drift or sticking linkages—can prevent a major unexpected shutdown down the line.

 

Summary

 

A Code 13 error on a generator means “Over Speed”—the engine is spinning faster than safe limits, so the system has shut down to prevent damage. This can be caused by components like the governor, throttle, or speed sensor malfunctioning, sudden changes in electrical load, or wiring issues. Because this error protects your equipment and ensures safety for everyone—whether it’s a family in St. Louis or a business in Nashville—it’s important to get a professional to inspect and fix the problem as soon as possible. Routine maintenance and prompt attention to error codes help keep your generator reliable and safe, ensuring backup power is there when you need it most.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the Code 13 Error on a Kohler Generator?

 

Understanding the Kohler Generator Code 13 Error

 

A Kohler Generator Code 13 error means the unit has experienced an “Overcrank” condition. This happens when the generator’s engine tries to start but fails to do so after several attempts. If you see this code, your generator is not producing power, which can be critical during outages in areas such as St Louis and Nashville where power reliability is essential for both residential and commercial properties. Fixing Code 13 involves identifying and resolving what caused your generator’s engine not to start.

 

What Causes Code 13 on Kohler Generators?

 

This error often occurs due to:

  • Low or no fuel supply (empty tank, closed fuel valve, or clogged filter).
  • Weak or dead generator battery.
  • Fuel quality problems (stale gasoline or diesel, contaminated fuel).
  • Blocked air intake, dirty air filter, or exhaust problems.
  • Ignition system issues (faulty spark plugs, bad ignition coils).
  • Problems with the oil level (low oil or faulty oil sensor).
  • Starter motor malfunction or wiring issues.
  • Faulty safety switches or failure of mechanical/electrical components.

 

Step-by-Step Instructions to Fix Code 13

 

Follow these steps in order. If you’re in St Louis or Nashville, having a professional service team nearby is always an option if the issue persists.

  • Check the Fuel Supply: Make sure your generator has fuel. For natural gas or propane units, ensure the gas valve from your supply line is open and you haven’t run out of gas. For diesel or gasoline models, visually inspect the fuel tank for adequate fuel. Refill or resolve any issues.
  • Inspect the Battery: The battery powers the starter motor. If the battery is weak, dead, or has corroded terminals, your generator’s engine might not crank effectively. Check for tight, clean connections. Attempt to jump-start the battery if necessary; if it doesn’t help, it may be time for a replacement.
  • Review Fuel Quality and Filters: Old or bad fuel can clog filters and injectors. If the fuel smells sour or has sat unused for months (especially after the off-season in St Louis winters or Nashville humidity), consider draining and refilling with fresh fuel. Replace the fuel filter if dirty or clogged.
  • Inspect the Air Filter and Intake: Dirty air filters can choke the engine. Remove the air filter and check for excessive dirt or blockage. Replace or clean the filter if needed. Make sure nothing is blocking the air intake or exhaust area around the generator.
  • Test for Ignition Spark: For gasoline engines, spark plugs are essential for starting. Remove a spark plug and inspect for fouling, wear, or wetness. Replace if necessary. Check that wires are securely attached, and there are no cracks.
  • Check Oil Level and Sensor: Low oil will keep the engine from starting. Open the oil cap and check the dipstick. Top off if necessary, ensuring you use the right oil type. If oil level is correct but Code 13 persists, the oil pressure sensor may be faulty and require replacement.
  • Starter Motor and Electrical Connections: Check that the wiring from the battery to the starter motor is tight, not frayed or broken. Listen as you try to start — a clicking sound with no turning means the starter may need repair or replacement. Burning smells or visible smoke call for immediate professional attention.
  • Safety Switches and Generator Control Panel: Some units come with safety switches that prevent startup (such as “Emergency Stop” buttons). Ensure all switches and circuit breakers are set to the “Run” or “On” position. Examine the controller for other error messages or warning lights.

 

Clearing the Code and Retesting

 

After inspecting and correcting any issues, reset your Kohler generator’s error code. Most models require you to:

  • Press the “STOP” button to clear alarms on the display.
  • Wait 30 seconds, then press “AUTO” or “RUN” to attempt restarting.

If the engine starts and runs normally, the problem is resolved. If it cranks but the code returns, double-check each step or seek expert help in St Louis or Nashville.

 

When to Call a Professional

 

Generators involve fuel systems, electrical wiring, and engine components that can be dangerous or tricky to service without training. If you’ve completed the steps above and the Code 13 error persists — or if you discover fuel leaks, significant electrical smells, or the generator won’t turn over at all — it’s time to get it professionally repaired.

In areas like St Louis and Nashville, technicians have the tools and safety knowledge to diagnose control board errors, sensor failures, and deeper fuel or electrical faults quickly and safely.

 

How to Prevent Code 13 in the Future

 

Preventing this error is mostly about good maintenance:

  • Run your generator regularly, even during off-seasons in St Louis or Nashville.
  • Keep the fuel tank filled with fresh fuel and change it out at least annually.
  • Replace filters and spark plugs according to the manufacturer’s schedule.
  • Keep the battery charged and check connections every few months.
  • Have a professional perform annual maintenance.

Taking these steps will ensure your Kohler generator is ready to run reliably — and will minimize future Code 13 shutdowns.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the Code 13 error code on a Kohler Generator?

 

What Does Code 13 Mean on a Kohler Generator?

 

When a Kohler generator displays a Code 13 error, it means the engine failed to start after several tries during an automatic or manual startup attempt. In simple terms, the generator attempted to start—usually up to three times—and couldn't get the engine running. This code doesn't point to a single cause, but rather to anything that might be preventing the generator's engine from starting correctly, even though the control system tried more than once.

 

Main Causes of Kohler Generator Code 13 Error

 

Even in places with frequent generator usage like St Louis or high seasonal storms as seen around Nashville, the reasons for a Code 13 can often fall into these categories:

  • Low or Dead Battery: The battery in your Kohler generator provides power to the starter and control system. If it’s weak, dead, corroded, or has loose connections, the engine won’t crank fast enough or at all.
  • Fuel Problems: Most residential and commercial generators in St Louis or Nashville use natural gas, propane, or diesel. If fuel valves are shut, tanks are empty, the fuel lines are clogged, or the fuel itself is stale, the engine can’t get what it needs to start.
  • Air Intake Blockages: Just like a car, the generator needs oxygen for combustion. Dirty or clogged air filters, animal nests, or debris blocking airways will keep the engine from starting.
  • Ignition Failures: This could mean spark plugs are dirty, worn out, or damaged—so the engine can’t ignite the fuel/air mix. Spark plug wires could also be damaged or disconnected.
  • Starter Issues: The starter motor or solenoid may have failed, preventing the engine from turning over. If you hear a click but the engine doesn’t crank, this is a common culprit.
  • Faulty Sensors or Switches: Sensors like the oil level sensor, temperature sensor, or safety switches (such as emergency stop) can fail or give false readings. Safety systems may prevent the generator from starting to protect the engine.
  • Control Board or Wiring Problems: Loose, corroded, or damaged wiring can break connections between parts. Sometimes the main circuit board, which tells the generator when and how to start, fails as well.
  • Cold Weather or Thick Oil: In cold places like winters in St Louis, oil can be too thick for proper engine start, or the cold can weaken batteries enough that starting is impossible without assistance.

 

What Actually Happens When Code 13 Is Triggered?

 

When your Kohler generator receives a signal to start (either because of a power outage or a manual request), it will go through a sequence:

  • Checks safety sensors to make sure it’s safe to start (oil level, coolant, emergency stop).
  • Tries to start the engine using the starter and battery.
  • If the engine doesn't start and run as expected within a set time, stops, and tries again for two or three attempts.
  • If all attempts fail, the control panel gives a Code 13—meaning “No Start (Overcrank)”.

Note that Code 13 means the generator never achieved normal running speed. If it started and then shut off, it would display a different code.

 

Why the Code 13 Error Is Common in St Louis and Nashville

 

Different climates bring their own challenges to generators in St Louis and Nashville. Cold snaps, long storage times, and infrequent exercise routines can create low battery voltage, water intrusion, fuel breakdown, and issues with rodents or insects nesting in air intake areas. Humid summers in Nashville can also encourage corrosion in electrical contacts and battery failure.

 

Summary of Possible Reasons for Code 13

 

To sum up, a Code 13 error on a Kohler generator means the engine failed to start after repeated attempts, usually due to:

  • Dead/weak battery
  • No fuel or restricted fuel system
  • Blocked or dirty air filters/intake
  • Bad spark plugs or ignition parts
  • Starter motor or electrical issues
  • Faulty sensors or safety switches
  • Main control board or wiring fault
  • Extreme weather conditions (cold, humid, hot)

For home and business owners in St Louis and Nashville, understanding these causes helps when discussing the situation with a professional or planning generator maintenance.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.