Generac Generator 3715 Error Code Explained: Meaning, Causes & Fixes

Discover what Generac Generator 3715 error code means, common causes, and step-by-step fixes. Quickly troubleshoot and restore your generator's performance.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the 3715 error code on Generac a Generator mean?

 

Understanding the 3715 Error Code on Your Generac Generator

 

When your Generac generator shows the 3715 error code, it means the unit has detected an "Undervoltage" issue. In simple terms, this means your generator is not producing enough electrical voltage during its operation, or the voltage it’s generating is below the expected range. For homeowners and businesses in St Louis and Nashville, understanding this code is important because it helps identify when there’s a problem that could prevent your generator from delivering the backup power you rely on during outages or emergencies.

 

What ‘Undervoltage’ Really Means

 

Normally, your Generac generator is designed to create a specific level of electricity—measured in “volts”—so it can safely and efficiently provide power to your home or business in St Louis or Nashville. When the generator produces less voltage than what’s required, sensitive appliances and systems may not work properly and can even become damaged. The 3715 error code alerts you to this kind of problem before any actual damage occurs.

 

Common Causes of the 3715 Error Code

 

There are several possible reasons your Generac generator might display the 3715 error code:

  • Loose or Damaged Connections: Electrical wires inside the generator can loosen over time or become damaged. Poor connections can lead to difficulty in maintaining the correct voltage.
  • Worn Out Brushes or Slip Rings: In some types of generators, components called “brushes” and “slip rings” help carry electrical current from the generator’s engine to your property. Worn or dirty brushes/slip rings can cause poor voltage output.
  • Voltage Regulator Failure: The automatic voltage regulator inside your generator controls the level of voltage output. If this part fails, your generator may not maintain the right amount of voltage, resulting in an undervoltage situation.
  • Overloaded Generator: If you try to run more appliances than the generator is rated for, the generator can become overloaded and produce less voltage than necessary, triggering the code.
  • Mechanical Engine Problems: Issues with the generator’s engine, such as lack of maintenance or other mechanical faults, can affect its ability to produce consistent voltage.
  • Faulty Breakers or Fuses: Breakers inside your generator may trip due to a fault, or a fuse may blow, lowering the voltage output.

 

Immediate Steps You Should Take

 

If you notice the 3715 code on your Generac generator in either St Louis or Nashville, there are some things you can safely do before calling a technician:

  • Power Down: Turn off the generator, especially if you hear unusual noises or smell anything odd.
  • Check Loads: Disconnect or turn off some of the appliances or equipment connected to the generator to see if it’s overloaded.
  • Inspect for Obvious Issues: Look for loose wires, visible damage, or any warning lights that may point to a specific problem area, but don’t attempt to repair electrical components yourself.
  • Review Maintenance Schedule: If regular generator maintenance hasn’t been performed recently, it could be a cause.

 

Why You Shouldn’t Ignore the 3715 Code

 

Continuing to run your generator with an undervoltage condition can do more harm than good. Low voltage can damage everything from refrigerators to sensitive electronics. For homeowners and business managers in St Louis and Nashville, addressing this error quickly preserves not just the generator, but also your appliances and peace of mind during a power outage.

 

Getting Professional Help in St Louis and Nashville

 

A qualified technician experienced with Generac generators should fully diagnose and repair issues causing the 3715 error code. They will test the electrical output, inspect internal connections, evaluate the voltage regulator and engine components, and ensure your system is safe and reliable. Whether you’re in St Louis or Nashville, having a knowledgeable professional handle this repair keeps your generator ready when you need it most.

 

Summary: What You Need to Know

 

The Generac 3715 error code means your generator is not producing enough voltage to safely power your home or business. It can be caused by a range of electrical or mechanical problems, or simply overloading the generator. If you see this code, turn off the generator, reduce connected appliances, and contact an experienced technician to fix the issue before it leads to more costly damage—especially critical in unpredictable weather that can affect both St Louis and Nashville.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the 3715 Error on a Generac Generator?

 

Understanding and Fixing the 3715 Error on a Generac Generator

 

A 3715 error on a Generac generator is a common problem that usually points to an "Undervoltage" situation while the generator is running. This means the generator is not producing enough electricity (voltage) for your home or business needs. This can be a concern for anyone in St Louis or Nashville who relies on their generator for backup power—especially during storms or outages.

If you've never worked with generators before, don't worry! Here's everything you need to know to address and fix the 3715 error safely and effectively.

 

What the 3715 Error Means and Why It Happens

 

The 3715 code refers to an "Undervoltage" alert that pops up when your Generac generator is putting out lower voltage than needed—typically below 80% of normal. Voltage is the electrical pressure that moves electricity, and if it's too low, your appliances and electronics may not run properly or could even get damaged. This can happen because of:

  • Problems with the generator’s voltage regulator (the part that keeps the voltage even).
  • Issues with the engine speed (like the generator not running fast enough).
  • Bad electrical connections or loose wiring.
  • Failed sensors or control board problems.
  • Dirty or clogged filters or mechanical problems inside the generator.

 

Immediate Safety Steps

 

Before doing anything further, focus on safety. Generators produce high voltage and can be dangerous to work on.

  • Turn off the generator if it's running—use the OFF switch on the controller.
  • If you have a manual transfer switch, flip it so your house is off grid power and NOT the generator.
  • Allow the generator to cool for at least 10–15 minutes before touching any part.

 

Basic Troubleshooting and Checks

 

  • Look at your generator’s control panel screen for the exact error. Write down any codes and messages you see.
  • Check the main circuit breakers—in some models, these are on the side of the generator. Make sure they haven’t tripped.
  • Open the unit (if comfortable), and look for any obvious loose wires. Sometimes, vibrations or weather in St Louis or Nashville can loosen things up.
  • Check for signs of rodent damage or corrosion, especially if your generator is outside.
  • Look at the air filter, oil level, and fuel level—make sure everything is within the recommended range (if the generator has been running for many hours, it might be time to check the oil and air cleaner).

 

Resetting the Error

 

If the issue seems minor or possibly a fluke, try resetting the code:

  • Switch the generator to "OFF" on the control panel, wait 30 seconds.
  • Switch to "MANUAL" or "AUTO" mode to power it back on.
  • Watch the control panel. If the 3715 error appears again, you’ll need a deeper fix.

 

Next Steps if the Error Persists

 

If the code keeps coming back, it’s usually a sign of one of these issues:

  • Faulty Voltage Regulator: This electronic part controls how much voltage the generator produces. If it fails, you will get low voltage. Replacing or adjusting it usually requires a licensed technician.
  • Slipping Engine Speed: If the generator engine isn’t running at the right speed (3600 RPM for most models), the voltage will be low. Listen for strange noises, rough running, or notice if maintenance is overdue.
  • Loose or Damaged Wiring: Any broken, chewed, or loose wires can interrupt proper voltage output. Only check further if you are comfortable with tools and safety. Otherwise, call a professional for further inspection and repairs.
  • Sensor or Control Board Problems: If the generator’s brains—the controller—are faulty, it can cause this error. This requires a skilled repair.
  • Bad Circuit Breakers: Occasionally, a breaker inside the generator short-circuits or gets stuck. This also needs professional help to test and replace.

 

When to Call a Professional

 

It’s always safest to contact someone with experience if you aren’t trained in generator systems—especially with electrics involved. In both St Louis and Nashville, expert technicians familiar with Generac systems (like those at full-service providers) have the tools to test voltages, replace a regulator, or track down an electrical problem safely.

Attempting repairs yourself—without experience—risks injury or more expensive damage.

 

How to Prevent the 3715 Error in the Future

 

Keeping your generator running smoothly is important for every home or business owner in St Louis and Nashville:

  • Get annual or semi-annual maintenance from a certified expert.
  • Keep the area around the generator clean and clear of debris.
  • Test your generator monthly (using the test mode or running it under a small load).
  • Immediately address any fuel, oil, or air filter issues.
  • Look for warning messages on the control panel and act quickly.

If your Generac generator is flashing a 3715 code, start with these checks, reset if possible, and do not hesitate to reach out for professional help in St Louis or Nashville for a complete fix. This keeps your power backup system reliable and safe throughout the year.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the 3715 error code on a Generac Generator?

 

Main Reasons Behind the 3715 Error Code on a Generac Generator

 

When a Generac Generator displays the 3715 error code, it’s telling you that the generator has detected a “Charger Missing AC” problem. In simple terms, your generator is letting you know it’s not receiving electricity from the power source it uses to keep its internal battery charged. This issue doesn’t mean that the main generator isn’t working, but rather that its battery charger isn’t getting the power it needs to keep the battery ready for emergency situations. This warning is very important for homeowners and businesses in St Louis and Nashville, especially during storm seasons when reliable backup power is vital.

 

What Does “Charger Missing AC” Actually Mean?

 

Your generator has a battery inside, just like a car, and this battery is always being charged with electricity when everything is connected properly. The “AC” part stands for “Alternating Current,” which is the type of electricity that comes from your wall outlets. When your generator can’t find this electricity coming in, it can’t charge the battery, and that’s when it throws the 3715 code.

In both residential and commercial settings in St Louis and Nashville, the battery plays a crucial role. If the battery dies because it isn't being charged, the generator might not start when the power goes out.

 

Reasons Why This Error Happens

 

There are several possible causes for the 3715 error, all related to why the generator’s battery charger is not receiving electricity:

  • Tripped or Turned-Off Breaker: The circuit breaker for the generator’s battery charger might have tripped (shut off automatically) or been switched off accidentally. This stops the flow of electricity to the charger, leading to the error.
  • Loose or Unplugged Power Cord: Sometimes the cord that connects the generator’s battery charger to the main power outlet gets unplugged or isn’t making good contact. In homes and businesses throughout St Louis and Nashville, vibrations, cleaning, or bumps could cause this.
  • Blown Fuse: The generator’s control panel or charger may have its own fuse. If this blows (burns out), it interrupts the path of electricity and causes a 3715 code.
  • Power Outage or Disconnected Utility Power: If there is a loss of utility power coming to the charger’s outlet (for example, if a whole house breaker is off or if there’s an outage in your area of St Louis or Nashville), the charger can’t work.
  • Damaged Or Faulty Battery Charger: If the battery charger itself is broken, even if it’s plugged in, the generator might think it isn’t getting AC power. This kind of failure can happen after years of service or due to lightning, power surges, or water damage that’s not uncommon in storm-prone areas near St Louis or Nashville.
  • Worn Or Broken Wiring: The electrical wires that deliver the AC power from your home or business’s breaker panel to the generator could be damaged, pinched, or disconnected. Animals or severe weather can sometimes be the cause.
  • Misconfigured Settings: In rare cases, if someone has changed the generator’s settings recently, it might not be set up properly to recognize the incoming AC power, which could generate a false error.

 

Why Does This Matter So Much?

 

If you see a 3715 error, it means your generator’s battery is not being kept charged. In St Louis or Nashville, if a power outage happens when the battery is dead, the generator won’t turn on automatically. This could leave a home or business without backup power just when it’s needed most.

So remember, the 3715 error points specifically to the battery’s charger not getting the AC power it needs—often caused by something simple like a tripped breaker or unplugged power cord, but sometimes related to deeper electrical or equipment failures. Identifying and resolving the cause ensures your generator will be ready for the next storm, outage, or emergency wherever you are in St Louis or Nashville.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.