Generac Generator 1910 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning behind Generac Generator 1910 error code, including common causes and effective fixes. Get your generator running smoothly with this easy guide.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the 1910 error code on Generac a Generator mean?

 

What the 1910 Error Code Means on a Generac Generator

 

When a Generac standby generator displays the 1910 error code, it means "Overcrank." Simply put, the generator tried and failed to start several times in a row and then automatically shut itself down to avoid damaging the engine. This error is common in both home and business generators – and it's a safety feature designed to protect your equipment.

 

Why Is the 1910 (Overcrank) Code Displayed?

 

The generator attempts to start (crank) for a pre-set number of cycles if it senses an outage or is asked to run. If it does not start within these attempts—usually after three tries—it posts the 1910 code and locks itself out. This stops further cranking, which could drain the battery or harm the starter motor.

There could be several reasons why your Generac generator in St Louis or Nashville isn’t starting properly. The most common causes are:

  • Low or empty fuel tank – The generator can’t run without fuel (usually natural gas, propane, or diesel).
  • Battery issue – If the battery is weak or dead, the starter motor can't turn the engine over fast enough to ignite.
  • Faulty spark plug or ignition system – Without a good spark, the air-fuel mixture inside the engine won’t ignite.
  • Clogged air or fuel filter – Fuel or air flow can be blocked, preventing the engine from getting what it needs to run.
  • Old or stale fuel (especially in portable models or those that use gasoline or diesel).
  • Mechanical failures – Problems with parts like the starter motor, fuel solenoids, or sensors can all trigger the overcrank code.
  • Low oil or low coolant (on liquid-cooled models) – Some generators won’t allow starting without proper oil or coolant levels because this could quickly damage the engine.

 

Immediate Steps to Take After a 1910 Error Code

 

If your Generac generator shows a 1910 code, here are practical actions anyone in St Louis or Nashville can take before calling in a professional:

  • Check the generator’s fuel level. If your unit runs on propane, make sure the tank valve is open and there’s enough fuel. For natural gas, check for local outages or supply problems.
  • Inspect and test the battery. A weak battery is one of the most common causes. If you have a multimeter, test for at least 12.4 volts. Replace or charge the battery if it’s weak or more than three years old.
  • Examine the area around the generator for obvious issues—blocked air intake, debris, or animals nesting inside (especially after long idle periods).
  • Try resetting the generator. This involves moving the control switch to “OFF” (wait 30 seconds), back to “AUTO,” then try starting again. Often, this clears false alarms after fuel or battery issues.
  • Review your owner’s manual. The troubleshooting section will be tailored to your exact model and may list specific checks or reset processes.

If these steps don’t resolve the problem, it's best not to keep trying to start the generator. Ongoing failed starts can cause further damage. At this stage, professionals who serve St Louis and Nashville can diagnose and safely repair more complex issues.

 

How Professionals Diagnose and Fix a 1910 Overcrank Issue

 

When a Generac generator in St Louis or Nashville needs repair for a 1910 error, experts follow careful steps:

  • Visual inspection – Checking for loose wires, corroded connectors, damaged fuel lines, or signs of leaks.
  • Battery load testing and cable inspection – Ensuring the battery provides full power and is free of corrosion or bad connections.
  • Testing fuel pressure and flow – For natural gas or propane units, professionals use special gauges to ensure proper delivery. Low pressure, clogs, or stuck regulators are common culprits.
  • Ignition system examination – Removing and checking the spark plug for wear and gap, verifying ignition coil performance, and making sure timing is correct.
  • Examining air filters and intake – Replacing dirty or clogged filters that can choke the engine.
  • Starter motor and solenoid assessment – Determining if these parts are drawing too much current or not engaging the flywheel correctly.
  • Checking for engine codes and reviewing error log – Many newer Generac models allow technicians to pull error histories for more targeted diagnostics.

Once the problem is located, professionals repair or replace faulty parts, clear the code using the control panel, and then test the generator to ensure it starts and runs reliably. After repairs, it’s also common to check for and update any software or firmware associated with the controller panel to prevent recurrence.

 

Preventing 1910 Errors in the Future

 

To greatly reduce the chance of a 1910 code on your Generac, regular preventative maintenance is important:

  • Operate the generator at least once a week using its automatic exercise cycle, or manually if necessary.
  • Check and top off fuel levels and ensure fuel valves and vents are open and unobstructed.
  • Replace batteries every 2–3 years, even if they’re still working, to avoid sudden failures.
  • Inspect and change spark plugs, air filters, and oil per the manufacturer’s schedule (usually every 1–2 years or 100 hours of operation).
  • Have qualified technicians service your generator at least annually, especially before storm season in St Louis or Nashville.

 

Summary: What to Know About the 1910 Error Code

 

A 1910 error code on your Generac generator means the engine has attempted to start and failed several times, so the system locked itself out to avoid damage. This is often a warning that there’s a fuel, battery, electrical, or mechanical problem. Homeowners and business owners in St Louis or Nashville can take some simple initial checks—fuel, battery, and reset—before seeking professional help for deeper issues or repairs. Preventative maintenance is the best way to avoid overcrank errors and keep your backup power ready when it’s needed most.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the 1910 Error on a Generac Generator?

 

Understanding and Fixing the 1910 Error on a Generac Generator

 

When you see a 1910 Error (Undervoltage Shutdown – Auxiliary Shutdown) on your Generac generator, it means the generator has shut down because it detected an unsafe low voltage condition, often linked to external wiring, device loads, or transfer switch connections. This is a safety feature to protect the system from electrical damage. Follow these detailed steps to resolve this error safely and effectively.

 

Check for Recent Outages or Transfer Switch Issues

 

If you’re in the St Louis or Nashville area, start by considering if your home or business recently experienced a power outage or flickering lights. The transfer switch is a device that switches your electrical source from the utility grid to your generator and back. A malfunction in the transfer switch can cause undervoltage errors. Listen for unusual clicking or buzzing from the switch, and visually inspect for burnt smells or scorch marks.

 

Check Main Utility Power

 

Make sure your property has a stable incoming power supply. Sometimes, the problem is with the electric utility and not your generator. Use a basic voltage meter (multimeter) to check your main power lines if comfortable, or simply verify if major appliances are working as expected. Inconsistent power will confuse your generator’s electrical sensing circuits and cause this shutdown code.

 

Visually Inspect Generator Cables and Connections

 

Turn off the generator’s main breaker before doing any checks, for safety. Open the generator’s exterior panel using the manufacturer’s instructions. Look at all visible wires, especially the larger ones entering and leaving the switch. Check for:

  • Loose or unplugged wires
  • Corrosion or rust on terminals (whitish-green powder or discoloration)
  • Bent or broken wire strands

If you see anything missing or damaged, do not attempt to repair it yourself; wiring mistakes are dangerous. In St Louis and Nashville, professional technicians from a licensed provider can diagnose and repair faulty electrical connections.

 

Check Generator Internal Components

 

Sometimes the error results from issues inside the generator itself, such as:

  • Loose internal connections—lightly press on wiring connectors to ensure they are securely in place, but never force anything.
  • Blown fuses—look for small glass or plastic fuses; replace if you see a break in the wire inside.
  • Dirty or damaged circuit boards—if you spot obvious black marks or burnt areas on the electronic components, the machine needs professional service.

If you’re not familiar with these parts, it’s safest to stop and call for service from a technician who regularly works with Generac generators in St Louis or Nashville.

 

Confirm There Are No Excessive Loads

 

Overloading your generator can trigger a 1910 error. Go inside and unplug unnecessary appliances or heavy electrical devices plugged in while the generator was running. Wait a few minutes, then clear the error as described below and start the generator again with reduced load.

 

Clear the 1910 Error Code

 

To reset the error:

  • Switch the generator to OFF (on the control panel), and let it sit for 30–60 seconds.
  • Turn the generator main breaker OFF to disconnect any internal loads.
  • Switch the generator to AUTO or MANUAL, then back to AUTO.
  • If the error code is still present, check for any additional trouble codes or blinking lights in the panel window. Write them down for a technician if needed.

If the code clears, restore power by turning the main breaker back ON, and observe the system.

 

When to Call a Professional

 

If you have followed all the above steps and the 1910 error persists:

  • The underlying cause may be something dangerous, such as a failing voltage regulator, alternator, or transfer switch.
  • There could be serious wiring or grounding issues that carry a risk of electric shock or fire.
  • Special diagnostic tools may be required for deeper electronic faults.

Generators are complex machines, and safe repairs require knowledge and special equipment. If you’re located near St Louis or Nashville, technicians at established service companies like Hoffman Brothers can quickly pinpoint and fix the problem, minimizing downtime and protecting your property.

 

Summary

 

To fix a 1910 error on your Generac generator: start by checking for recent outages, verify utility power and transfer switch functionality, inspect visible wires and internal components carefully, and reduce any overload. Always reset the generator with the correct process, and call a professional if the error doesn’t clear. Safety first—if you’re ever unsure, contact a trained technician in St Louis or Nashville for help.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the 1910 error code on a Generac Generator?

 

What Causes the 1910 Error Code on a Generac Generator?

 

The 1910 error code on a Generac generator means there’s a problem with the generator’s battery charger. To put it simply, this code shows up when the generator is either not receiving power to charge its battery, or the internal battery charger isn’t working as intended. The result is a battery that’s not being kept charged, which can prevent the generator from starting up when you need it most. Whether you’re in St Louis or Nashville, battery charger issues are a leading cause of generator startup problems, especially in climates with big temperature swings.

 

Understanding What the Battery Charger Does

 

The generator’s battery charger is a small device—either built-in or attached—that keeps the starting battery charged. This charger usually works off your home or building’s incoming electrical power. When everything’s working, the generator battery is always topped off and ready to go. If the charger stops functioning, the battery can lose power slowly over time, and the generator won’t start—even if everything else is working perfectly.

 

Key Reasons Why the 1910 Error Code Appears

 

  • Loss of Incoming Power to the Charger: If there’s no utility power (from the electric company) at your property in St Louis or Nashville, then the generator’s charger can’t do its job. This might happen if a circuit breaker is tripped, a fuse is blown, or a GFCI outlet has popped.
  • Faulty Battery Charger: Sometimes, the actual charging device inside the generator fails. This can be due to age, moisture, lightning strikes, or wiring issues.
  • Damaged Wiring or Connections: Wiring connects the charger to the battery and the generator’s control board. If there’s corrosion, loose wires, or rodent damage (common in both St Louis and Nashville), the charger won’t work properly, and you’ll see the 1910 code.
  • Blown Fuse Inside the Charger Circuit: Many Generac units include a fuse to protect the charging system. If this fuse blows, perhaps after a power surge or storm, the charger stops operating.
  • Internal Generator Control Board Failures: Rarely, the electronic “brain” of the generator can have an internal failure or software glitch, causing false readings or even shutting off charger operation—leading to the 1910 code.
  • Battery Problems Detected by the Charger: Sometimes, the code comes up if the charger detects an issue with the battery itself, such as a bad cell, excessive corrosion at the terminals, or a short circuit. While this isn’t the most usual cause, it shouldn’t be ignored.

 

Why This is Important for St Louis and Nashville Homeowners and Businesses

 

The 1910 error code is common in areas with big differences between hot summers and cold winters, such as St Louis and Nashville. Variations in temperature stress battery components, wiring, and chargers. Humidity and storms increase the risk of electrical surges that can blow fuses or damage charging circuits. In both residential neighborhoods and commercial sites, the battery is the heart of the generator startup process. Missing this error can mean no backup power when it’s needed most—during storms, ice, or grid failures.

 

Things That Can Make the 1910 Error Code Worse

 

  • Very old batteries or chargers that have not been serviced regularly
  • Rats, mice, or squirrels chewing wiring (a risk in storage sheds or utility closets in both St Louis and Nashville)
  • Water leaks inside the generator housing causing rust or shorts
  • Turning off the home’s main electrical panel breakers for long periods
  • Skipping routine maintenance checks, especially before storm season

 

Summary of What the Code Means

 

In summary, the 1910 error code on a Generac generator signals a problem with the battery charger or related parts. The error means that, unless something changes, the generator’s battery will eventually go dead, and the unit won’t be able to start up when utility power goes out. Home and business owners in both St Louis and Nashville rely on these chargers to keep backup power ready year-round, so understanding the meaning behind the code is key to keeping your generator ready for any emergency.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.