Generac Generator 1903 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and effective solutions for Generac Generator 1903 error code. Quickly troubleshoot and resolve 1903 errors with this comprehensive guide.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the 1903 error code on Generac a Generator mean?

 

Understanding the 1903 Error Code on a Generac Generator

 

When your Generac generator displays the 1903 error code, it is indicating an “Under-speed” or “RPM Sense Loss” fault. In simple terms, this means that the generator's engine is not running at the correct speed, or the control system is unable to detect how fast the motor is spinning. Generators need to run at a specific speed to produce the right amount of electricity (measured in hertz); when they slow down, speed up unexpectedly, or lose the ability to detect their own speed, it can result in problems with power output or even damage sensitive appliances.

 

What Causes the 1903 Error Code?

 

A 1903 fault usually occurs because:

  • There is a problem with the speed sensor, also called the RPM sensor, which tells the generator's computer how fast the engine is working.
  • The engine itself is failing to maintain a consistent speed—often due to fuel supply issues, mechanical problems, or improper load.
  • Corrosion, loose wiring, or broken connectors are preventing electrical signals from reaching the control board.
  • There is a problem with the electronic control board inside the generator.
This error code can be seen in both home and business backup Generac units, and is a frequent service call in both St Louis and Nashville, especially during peak seasons for storms or power outages.

 

Signs and Symptoms Linked to 1903 Fault

 

When the 1903 code appears on your Generac generator, you might notice:

  • The generator tries to start but shuts down quickly.
  • An alarm or warning light may flash on the control panel.
  • You may not have any backup power when the main power goes out.
  • The display panel will usually read "Under-speed," "RPM Sense Loss," or specifically show “1903” as the error code.
Customers in St Louis and Nashville often report that the generator seems to “struggle” or make unusual sounds just before this error appears.

 

Common Causes Specific to Generac Generators

 

  • Dirty or Clogged Air Filter – Airflow restriction makes it hard for the engine to breathe, leading to low speed.
  • Fuel Pressure Problems – Low or inconsistent fuel flow (natural gas or propane) may starve the engine, making it run slow or stall.
  • Mechanical Engine Problems – This could include issues with the throttle, governor, spark plugs, or ignition coil failing to keep the speed constant.
  • Faulty or Disconnected RPM Sensor – The sensor that tells the generator how fast it’s spinning might be broken, dirty, or have a bad connection.
  • Electrical Connection Issues – Vibration, corrosion (especially in humid areas like Nashville), or rodent damage to wires can interrupt signals.
  • Control Board Failure – Less common but possible, the main electronic “brain” of the unit could be malfunctioning.

 

What Should I Do if My Generator Shows 1903?

 

If you see the 1903 fault code, here are steps you can take before calling a technician:

  • Turn the generator off completely—flip the switch to the “OFF” position and wait a few minutes.
  • Visually inspect the unit for obvious damage, loose wires, or debris around air intake and exhaust areas.
  • Check or replace the air filter if you are comfortable doing so.
  • If accessible, check for leaks in fuel lines or a closed fuel valve (make sure the fuel is turned on).
  • After checking, switch the generator back to “AUTO” mode and try a manual start.
If the generator still displays the 1903 error code or does not start properly, do not attempt advanced repairs yourself. If you are in St Louis or Nashville, contact a professional generator service like Hoffman Brothers for reliable and safe troubleshooting and repair.

 

Why Professional Inspection is Important

 

Gasoline, propane, or natural gas generators can pose safety hazards such as electric shock, fire, or gas leaks. The 1903 error involves many components—fuel system, wires, electronic boards, and moving parts. An experienced technician will:

  • Use diagnostic tools to confirm if the engine is actually running slow or if it’s a false signal from wiring or the RPM sensor.
  • Check electrical and sensor connections for corrosion, looseness, or rodent damage.
  • Test the air-fuel mixture, engine operation, and load balance.
  • Inspect and clean or replace RPM sensors and related components as needed.
  • If necessary, reprogram or replace the generator’s main control board.
Homeowners in both St Louis and Nashville find that professional generator maintenance can prevent most error codes and ensure the unit is always ready for outages.

 

Preventing Future 1903 Errors

 

Regular generator maintenance—changing filters, checking fuel supply, cleaning electrical connections, and running periodic self-tests—greatly reduces the chance of experiencing a 1903 error code. Local weather in St Louis and humidity in Nashville may demand even more frequent checks for corrosion or debris. Scheduling annual professional inspections and promptly addressing any engine trouble is the best way to keep your generator reliable.

 

In Summary

 

The 1903 error code on a Generac generator means the engine is not running at the right speed or the system can’t detect its speed. This often involves minor sensor or wiring issues, but can be caused by deeper engine or fuel problems. While there are a few quick things you can check yourself, it’s safest to call in a certified generator specialist, especially for residents and businesses in regions like St Louis and Nashville. Regular service and prompt attention to warning codes will protect your backup power source for years to come.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the 1903 Error on a Generac Generator?

 

How to Fix the 1903 Error on a Generac Generator

 

The 1903 error on a Generac generator is an “Undervoltage” alarm, which means your generator detected that the voltage it’s producing has dropped below the expected safe level. This typically happens due to three main reasons: low generator output because of a mechanical problem, an electrical issue (like a failed voltage regulator), or a loose connection. Here’s exactly what you need to do to safely and thoroughly troubleshoot and correct this problem in your home or business, whether you’re in St Louis or Nashville.

 

Check Your Generator’s Status and Reset the Error

 

  • First, safely approach your generator. Make sure your hands are dry, and you have protection from rain and any moisture if the unit is outdoors.
  • Locate the generator’s control panel—this is usually a small digital screen with navigation buttons.
  • The 1903 error message will show up on this control panel. Before you do anything else, write down the error code and any messages that appear for reference.
  • Attempt to clear the alarm by pressing the "Off" button. Wait a full minute, then press "Enter" or another “Reset” option available, and finally try to switch your generator back to “Auto”.
  • If the error resets and your generator starts as expected, monitor its output and listen for unusual noises.

 

Check for Simple Issues: Fuel, Battery, and Connections

 

  • Open the generator’s access panel (use a screwdriver if necessary, but make sure the generator is off). Ensure the battery terminals are clean, tight, and not corroded. Loose battery cables can cause control errors.
  • Look for any visibly loose or disconnected wires inside the generator. Don’t fix anything with the generator on; all maintenance should be done with the generator safely turned off.
  • Check fuel supply—make sure the propane or natural gas line is open and your tank is not empty. Low gas pressure or empty tanks will prevent correct voltage output.

 

Inspect the Circuit Breakers and Loads

 

  • On the generator’s exterior, find its main breaker. Make sure it is fully switched to the ON position. If you see a tripped breaker (switched to the OFF position), switch it off, then back on firmly.
  • If the generator is powering your home or business, unplug any heavy appliances to test if one is overloading the unit. Sometimes sudden large loads can cause undervoltage.

 

Listen and Look for Mechanical Problems

 

  • Start the generator (switch to “Manual/Auto”). Listen closely for any unusual sounds such as sputtering, grinding, or knocking—these could indicate mechanical issues that require a specialist, like the team in St Louis or Nashville, to inspect further.
  • Check for visible oil leaks, coolant leaks, or broken fan belts (if visible). Any of these can impact the generator’s internal systems and reduce its ability to produce correct voltage.

 

Check Voltage at the Outlets (If You Have a Voltmeter)

 

  • If you feel safe doing so, and only if you are familiar with a voltmeter, check the generator’s power output at a standard outlet. Be extremely cautious and ensure the voltmeter is on the correct AC voltage setting.
  • Typical output should read between 120-130 volts per outlet. If readings are consistently much lower, the voltage regulator or alternator may be at fault.

 

When to Call a Professional Electrician or Generator Technician

 

  • If you’ve tried all the steps above and the 1903 error returns, it’s time to reach out for professional help in St Louis or Nashville. The problem could be a faulty Automatic Voltage Regulator (AVR), damaged wiring, or even a failed alternator—these are best handled by trained technicians.
  • Attempting deeper troubleshooting (like opening the voltage regulator or testing windings) without experience is dangerous and could void your warranty.

 

Preventing Future 1903 Errors

 

  • Schedule regular annual maintenance with experts in St Louis or Nashville. Preventive care includes inspecting and tightening all electrical connections, checking for fuel problems, and servicing critical generator components so voltage issues are caught before they trigger shutdowns.
  • Always keep the generator area clear of debris, rodents, and insects, as these can cause wiring damage or short circuits.
  • Make sure automatic exercise cycles (weekly self-tests that Generac generators perform) run without interruption, as these keep internal components lubricated and charged.

 

Fixing the 1903 error involves some basic checks like resetting the control, verifying fuel and breakers, and listening for engine issues. If the error doesn’t clear or returns often, you need a certified generator specialist in St Louis or Nashville to safely assess and repair your equipment, ensuring your property stays powered and protected.

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the 1903 error code on a Generac Generator?

 

What the 1903 Error Code Means on a Generac Generator

 

The 1903 error code on a Generac generator signals the generator is having a problem related to "RPM Sense Loss." In simple terms, it means the generator's system can't reliably detect how fast the engine is spinning. This is a critical measurement, since the right engine speed ensures your generator in St Louis or Nashville produces reliable, safe power for your home or business.

 

Why Engine Speed Matters

 

A generator converts the motion of its engine (mechanical energy) into electricity. It must turn at a precise speed—measured in revolutions per minute, or RPM—to make the right amount of power. If the system loses track of RPM, it will instantly shut things down to prevent damage.

 

Main Causes Behind the 1903 Error Code

 

Many things can cause RPM sense loss on a Generac unit. Here’s a detailed breakdown that applies to many Generac generator models in use throughout St Louis and Nashville:

  • Faulty RPM Sensor: Most modern generators use a sensor (sometimes called a magnetic pickup or flywheel sensor) to "read" how fast the engine is spinning. If the sensor fails, gets dirty, or the wiring to it becomes loose or corroded, the generator can’t get that information, triggering the 1903 code.
  • Problems with the Control Board: The control board is like the brain of the generator. If the circuit inside the board that reads the RPM info goes bad, it can’t understand the speed—even if the sensor is working correctly.
  • Mechanical Engine Problems: Issues inside the engine—like a seized engine, broken flywheel teeth, or internal mechanical wear—can stop the engine from spinning at the right speed, or stop it from spinning at all. The system registers this as a loss of RPM signal and generates the error.
  • Electrical Connection Issues: Loose, broken, dirty, or oxidized connectors between the RPM sensor, the engine, or the control board can interrupt the signal. This is especially common after seasonal changes in humidity or after rodents disturb wiring, which is something technicians frequently see in both St Louis and Nashville installations.
  • Low Battery Voltage: All the sensors and the control board need steady electricity to work properly. If the generator’s battery is weak or failing, or the charging system isn't charging properly, it can cause all sorts of strange errors—1903 among them.
  • Overloaded Generator: Trying to power too many things at once can cause the engine to bog down, causing RPM to drop lower than what’s safe. The control board will register this as an RPM loss and shut the generator down, showing the 1903 code.

 

Conditions Unique to the St Louis and Nashville Areas

 

Generators in St Louis and Nashville often face specific challenges that can lead to the 1903 code. For example, fluctuating weather—humid summers, cold winters, and spring rains—can introduce moisture into outdoor enclosures, causing corrosion or rust on sensor contacts. In neighborhoods and rural areas alike, small animals (mice, squirrels) sometimes chew through wiring, interrupting the RPM signal pathway.

 

Summary of Everything That Can Trigger the 1903 Code

 

To recap, the main causes behind a 1903 RPM Sense Loss error are:

  • A malfunctioning or dirty RPM sensor
  • Issues with the control (brains) of the generator
  • Mechanical trouble within the engine itself
  • Damaged or loose electrical connections or wiring
  • Weak or disconnected battery affecting control systems
  • Overloading the generator beyond its rated capacity
  • Environmental factors specific to regions like St Louis and Nashville (such as rodents or corrosion)

If you see the 1903 code, this means the generator is unable to accurately sense its engine speed, and it’s shutting down to protect itself and your property. Understanding these root causes can give you a comprehensive idea of what's happening, so you know what’s in play before any professional diagnosis or fix takes place.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.