Generac Generator 1202 Error Code Explained: Meaning, Causes & Fixes

Discover what Generac Generator 1202 error code means, its common causes, and how to fix it quickly. Learn troubleshooting tips to get your generator running smoothly again.

Reviewed by Content Team

Head of Content, D. Gorenko

Updated June, 5

What does the 1202 error code on Generac a Generator mean?

 

What the Generac 1202 Error Code Means on Your Generator

 

If your Generac generator is showing the 1202 error code, it means your generator has detected a “Low Oil Pressure Shutdown.” This is a safety feature that instantly stops the generator’s engine to prevent damage when it senses that the oil pressure is too low for safe operation. In simple terms: your generator stopped running to protect itself because it doesn’t have enough oil pressure.

 

Breaking Down the 1202 Code: Why Oil Pressure Matters

 

Oil pressure is vital in any engine, including those in standby and backup generators like Generac models commonly found in both St Louis and Nashville homes and businesses. Oil lubricates the moving parts inside the engine, reducing friction and preventing the motor from overheating. Without proper oil pressure, metal components would rub directly against each other, causing fast and severe engine damage—sometimes within minutes.

The 1202 code is programmed to keep your generator safe. When sensors register that oil pressure has dropped below a critical threshold, the control panel shuts the generator down and displays this error. This can prevent catastrophic damages, such as a seized engine, which are much more expensive to repair than anything causing a 1202 error.

 

What Causes a 1202 Low Oil Pressure Shutdown?

 

There are a few common reasons you might see the 1202 code on your Generac generator in St Louis or Nashville:

  • Low Oil Level: If the engine doesn’t have enough oil, oil pressure drops, and the 1202 code appears. This is the most frequent cause.
  • Oil Leak: Leaks from seals, gaskets, filters, or drain plugs can reduce oil levels and make it impossible to maintain pressure.
  • Wrong Type or Old Oil: Using oil that’s too thin, thick, or dirty means it won’t provide correct lubrication or pressure. Always use the oil recommended in your owner’s manual.
  • Faulty Oil Pressure Sensor: Rarely, the sensor that reads oil pressure can break or malfunction, showing a false 1202 error.
  • Engine Wear or Internal Problems: In aging generators, worn engine bearings can make it impossible to build enough oil pressure. This is more common in older, rarely-serviced units.
  • Clogs in the Oil Pathway: Very dirty oil or sludge can clog passages, restricting oil flow and reducing pressure.

 

Step-by-Step What To Do If You See 1202 On Your Generac Generator

 

  • Don’t Try to Restart: Restarting without fixing the issue could cause expensive engine damage.
  • Check the Oil Level: Make sure your generator is off and has cooled. Remove the dipstick and check if the oil level is between the “add” and “full” marks. Top up if needed, using the right oil type for your climate.
  • Look for Oil Leaks: Inspect around the base, oil filter, and drain plug. Any pooling oil or oily residue is a sign of a leak that a technician should fix.
  • Assess Oil Condition: See if the oil looks dark and dirty, thick, or watery. If it hasn’t been changed recently, a fresh oil and filter change can resolve issues.
  • Reset the Error Code: If you top up the oil, use your generator’s control panel to clear/reset the error. Most Generac models have a “reset” or “enter” button for this purpose.
  • If the Error Returns: If the 1202 error appears again after you’ve checked oil level and quality, or if you find a leak or hear odd noises from the generator, stop immediately and call a professional technician. This could mean a mechanical issue or a problem with the oil pressure sensor.

 

Importance of Regular Maintenance in St Louis and Nashville Climates

 

Regular generator maintenance is the best way to prevent the 1202 error. Both St Louis and Nashville experience temperature extremes—cold winters can make oil thicken, and hot summers can degrade oil faster. Seasonal oil and filter changes, as well as regular full-system inspections, will keep your equipment working properly and reduce the risk of seeing low oil pressure shutdown codes during critical times.

 

When to Call a Generator Specialist

 

If you’re unable to resolve the 1202 code with the steps above, or if you’re uncomfortable checking oil and troubleshooting, contact a local generator service expert. In both St Louis and Nashville, it’s not uncommon for these issues to be quickly resolved by professionals, minimizing downtime and protecting the investment you’ve made in backup power for your home or business.

 

Summary: 1202 Error Code Means “Low Oil Pressure”

 

To recap, the 1202 error is your Generac generator’s way of telling you it needs immediate attention due to low oil pressure. In most cases, it’s caused by low oil level, dirty oil, or a leak, but other mechanical or electrical faults can be to blame. Addressing this issue fast will keep your generator running when you need it most, which is especially important for families and businesses in both St Louis and Nashville who depend on reliable backup power.

Expert Generator Solutions Await!

Generator issues in St. Louis or Nashville? Our experts provide quick repairs and maintenance to keep you cool. Contact us today!

Request a quote

How to fix the 1202 Error on a Generac Generator?

 

What the 1202 Error Means on a Generac Generator

 

When your Generac generator displays the 1202 error code, it means there is a "Low Oil Pressure Shutdown." This safety feature automatically turns off the generator engine to prevent it from running when the oil pressure is dangerously low, protecting the engine from severe damage. In the areas of St Louis and Nashville, homeowners and businesses rely on standby generators especially during severe weather, and this error is one of the more common service calls.

 

Why the 1202 Error Occurs

 

This error may be triggered by:

  • Insufficient oil in the generator’s engine
  • Oil that is dirty or broken down
  • A faulty oil pressure sensor or switch
  • A wiring or connection problem to the oil pressure circuit
  • Running the generator on an incline, which may affect oil level readings
If you are located in St Louis or Nashville, these issues may be more likely after a long period of generator inactivity, or following a severe storm that caused your generator to run for an extended time.

 

Step-by-Step Instructions to Fix the 1202 Error

 

  • Ensure Safety First: Before touching the generator, make sure it is completely turned off. Switch the main power switch to the OFF position. Wait a few minutes to allow any moving engine parts to stop and for the system to safely power down.
  • Check the Oil Level: Open the generator’s access panel, usually located on the side of the unit. Locate the dipstick — this is similar to a car engine’s dipstick. Remove it, wipe it clean, then reinsert and withdraw it again to check the oil level. The oil mark should be between the two notches/holes on the dipstick. If the oil is below the minimum mark, add the type of oil specified in your generator manual.
  • Inspect the Oil Quality: Examine the oil’s color and texture. If it appears dark, gritty, or smells burned, it’s time for an oil change. Dirty oil loses its lubricating ability and can trigger a low oil pressure reading. Drain the old oil according to the manufacturer’s instructions, install a new oil filter (if equipped), and refill with fresh oil up to the proper level.
  • Check for Oil Leaks: Look around and under the generator for any signs of leaking oil, as this can drop oil levels and pressure over time. Repair any leaks before restarting — persistent leaks require the attention of a trained technician in St Louis or Nashville.
  • Examine the Oil Pressure Sensor: The oil pressure sensor (sometimes called an oil pressure switch) is a small component that tells the generator’s control board if oil pressure falls below safe levels. The sensor is usually connected to the engine block and may have one or more wires attached. If the oil level and oil quality are correct but the 1202 fault persists, make sure the electrical connector is secure and free of corrosion. If you’re not comfortable checking this, technicians in St Louis and Nashville are experienced in handling these components.
  • Reset the Error Code: Once the oil situation is corrected, and you’ve checked the sensor and wiring, you need to clear the 1202 error. On most Generac generators, do this by moving the control switch to OFF, then back to AUTO after a few seconds. Some models may require holding down the ENTER or OFF button for a few seconds depending on the control panel.
  • Run a Test Cycle: With the generator set to AUTO, initiate a manual test. This usually means pressing the MANUAL or TEST button on the control panel. Observe the start-up for a few minutes. If the generator runs continuously without re-triggering the 1202 error, the problem is resolved.
  • If the 1202 Error Returns: If the 1202 error shows up again immediately, despite proper oil levels and clean connections, the oil pressure sensor may be faulty, or there may be a wiring issue. At this point, a professional technician familiar with Generac generators in St Louis or Nashville should be called for diagnosis and repair, as operating with low oil pressure can permanently damage your engine.

 

When to Seek Professional Help

 

If you have checked and corrected the oil, inspected for leaks, and looked over basic connections but the problem continues, it’s time to consult a certified technician. Generator engines are sensitive machines, and it’s much less expensive to fix a minor part now than to replace an engine later. Residents and businesses across St Louis and Nashville know that prompt, knowledgeable service keeps your generator ready and reliable in any emergency.

 

Quick Tips to Prevent Future 1202 Errors

 

  • Check your generator’s oil at least twice per year, or after each time it runs for more than 24 hours continuously.
  • Use only the oil type recommended in your manual — using the wrong oil can lead to pressure issues.
  • Have annual maintenance performed by a professional technician in St Louis or Nashville.
  • If you notice oil stains, drips, or a burning oil smell, have your generator inspected immediately to avoid automatic shutdowns when you need power most.

 

Areas Of Expertise

We treat our people as our top priority so they'll treat you the same way. 100% Satisfaction, Every Time!

Air Conditioning

Providing air conditioning repairs, installation and maintenance for St Louis, MO and Nashville, TN. During the hot summers, call Hoffmann Brothers for all your AC repairs, replacement, and tuneup needs.

Electrical Repair

Hoffmann Brothers offers residential and commercial electrical services for St Louis homes and businesses. Lighting, outlets, panels, whole house fans, generators, and more. Call our licensed electricians today!

Heating Services

Need a furnace repair in St Louis or Nashville? Hoffmann Brothers can handle all your heating repairs, no matter the brand, including ductless mini-split systems. We also proudly offer heating system installations, and ongoing maintenance services.

Appliances

Hoffmann Brothers offers appliance repair services throughout St Louis, MO! Our experienced technicians are trained to work on all major brands of most home appliances including Dishwashers, Refrigerators & Freezers, Washing Machines & Dryers, and Ovens.

Plumbing Services

Hoffmann Brothers is your experienced Plumbing Company service both St Louis and Nashville. We offer plumbing repairs and installations, along with drain and sewer solutions.

Commercial Services

Do you need Mechanical or Commercial services for your St Louis or Nashville area business? We offer HVAC, Plumbing, Electrical (St Louis only), Indoor Air Quality, and more.

Water Heaters

Hoffmann Brothers is your professional water heater contractors for both Nashville, TN and St Louis, MO. We provide hot water heater installation, repair, and maintenance for both standard and tankless systems.

Drains & Sewers

Hoffmann Brothers is your Nashville and St Louis area drain Plumber. We provide drain cleaning and clearing and much more. Trust our drain experts to fix your clogged sink or toilet quickly and efficiently.

What could be causing the 1202 error code on a Generac Generator?

 

What Causes the 1202 Error Code on a Generac Generator?

 

The 1202 error code on a Generac generator points to a “Low Oil Pressure Shutdown.” In very simple terms, this means your generator’s engine has detected that the oil pressure is too low for safe operation, so the system shuts down to protect itself from serious damage. Every engine, including those in backup generators across both St Louis and Nashville areas, depends on oil to keep its internal parts lubricated, reduce friction, and help with cooling. Without enough oil pressure, moving parts can grind together, overheat, and cause permanent damage. That’s why the generator’s safety system watches oil pressure very closely and shuts down right away if something’s wrong.

 

Main Reasons the 1202 Error Code Happens

 

The 1202 error is specific, but the causes behind it can be varied. Here’s what could trigger it:

  • Low Oil Level: The simplest and most common reason is that there’s not enough oil in the engine. Over time, oil can leak out (sometimes from gaskets, seals, or drain plugs), burn off during normal use, or get lost if the generator sits unused for a while.
  • Oil Dilution or Contamination: If the oil is dirty, mixed with fuel, coolant, or even water (sometimes caused by condensation or a failing gasket), it can’t lubricate or pressurize the engine as well as it needs. In the humid climate of St Louis or after heavy storms in Nashville, condensation inside the generator is not uncommon, which can contaminate the oil.
  • Oil Pressure Sensor or Switch Failure: Generac generators use an oil pressure sensor (sometimes called a sender or switch) to “read” how much pressure is present. If this part itself malfunctions—whether due to age, wear, or brief electrical issues—it might incorrectly report a low oil pressure problem, even when there isn’t one. This is especially true for generators that have experienced frequent cycling due to the unpredictable weather patterns found in both St Louis and Nashville.
  • Oil Pump Malfunction: The oil pump is responsible for moving oil throughout the engine. If it fails or gets clogged (by sludge, old oil that’s broken down, or debris), the oil won’t reach all the engine parts, and the pressure will drop. This can happen as generators get older or when routine oil changes are missed, a concern in high-usage areas like St Louis’s commercial sites or Nashville housing communities.
  • Internal Engine Problems: Sometimes, internal engine wear—like worn-out bearings or piston rings—prevents the engine from holding proper oil pressure, even when the oil level seems okay. While less common, this can occur in generators that have run for thousands of hours without major maintenance. This situation is occasionally seen in older properties or commercial settings throughout St Louis and Nashville.
  • Wrong Oil Type or Viscosity: Each generator needs a specific type of oil, often outlined in the manual. Using oil that’s too thin (low viscosity) or too thick can prevent the system from building proper oil pressure, especially during temperature swings experienced in St Louis winters or hot Nashville summers.
  • Crimped, Blocked, or Leaking Oil Lines: The tubing or passages that carry oil can get blocked by gunk, or may kink/leak after a physical impact or improper maintenance, especially after installation or servicing. If oil can’t circulate as designed, pressure drops and the engine will signal an error.

 

How the Generator Detects and Reacts to Oil Pressure Issues

 

Modern Generac generators, whether installed in homes or businesses from St Louis to Nashville, use an oil pressure sensor that “reads” how hard the oil is being pushed around the engine. If this level falls below a certain safe point—even for a moment—the generator tells its controller to shut things down and displays the 1202 error code. This system is designed to prevent catastrophic engine damage, acting like a watchdog so you don’t risk expensive repairs or a failed backup system when you need it most.

 

Summary of What Could Cause the 1202 Error Code

 

The 1202 error code is always about not enough oil pressure inside your Generac generator’s engine. That can happen because there isn’t enough oil, the oil is dirty or contaminated, the oil pump or the sensor isn’t working right, or there are internal engine problems. For property owners across St Louis and Nashville, paying attention to oil levels, the kind of oil used, and regular maintenance are the best ways to prevent these causes. Knowing what this code means and what might cause it helps you work with professionals quickly and ensures your standby power stays ready when you need it.

SERVING

St. Louis & Nashville Areas

Brentwood, MO
1025 Hanley Industrial
Brentwood, MO 63144

Nashville, TN
45 Willow St.
Nashville, TN 37210

Call Our St. Louis Office

Call Our Nashville Office

Nashville Location

(615) 515-3015

Read More

Kohler Generator Code 21 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 21 means, its common causes, and how to fix it. Get quick troubleshooting tips to resolve this error and keep your generator running smoothly.

Kohler Generator Code 24 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 24 means, common causes behind this error, and step-by-step solutions to fix it. Quickly troubleshoot your generator with our expert guide.

Kohler Generator Accy PwrOver Warning Error Code Explained: Meaning, Causes & Fixes

Discover what the Kohler Generator "Accy PwrOver Warning" error code means, its common causes, and how to fix it. Get clear, step-by-step solutions to keep your generator running smoothly.

Cummins Generator SPN 175 FMI 3 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for the Cummins Generator SPN 175 FMI 3 error code. Learn how to diagnose and fix this issue to keep your generator running smoothly.

Kohler Generator Code 23 Error Code Explained: Meaning, Causes & Fixes

Discover what Kohler Generator Code 23 means, common causes behind the error, and effective solutions to fix it. Get your generator running smoothly with these expert tips.

Cummins Generator SPN 284 FMI 4 Error Code Explained: Meaning, Causes & Fixes

Discover the meaning, common causes, and solutions for Cummins Generator SPN 284 FMI 4 error code. Quickly troubleshoot and resolve this generator issue with our expert guide.